The displayed price covers the container unit only. Miners are sold separately.
Contact us for shipping and lead time.
BITMAIN ANTSPACE HW7 is a 2000kW hydro cooling container that supports either 396 standard T-type Antminer hydro miners or 242 new 2U Antminer S23e U2H units. It combines a dry cooler and water-curtain cooling system, operates from -40°C to 50°C, and is designed for high-density hydro mining deployment. Contact LeedMiner for current pricing, site planning and delivery.
The items below come from the current product description and catalog fields; final package scope is confirmed in the quote.
Review the catalog specifications and request a site-specific configuration.
Use the published specifications as a starting point. Confirm the final package against your site and miner fleet before ordering.
Check available capacity, voltage and connection design for the intended full load.
Review water-loop or ventilation interfaces, ambient conditions and heat rejection at the deployment site.
Confirm miner compatibility, included components, installation scope, delivery location and lead time in the quote.
| Model | ANTSPACE HW7 for 2U/T-type |
|---|---|
| Capacity | 396 |
| Cooling | Hydro Cooling |
| Power Consumption | 2000 kW |
| Input Voltage | 380–480V, 50/60Hz |
| Electrical input | 380–480V, 50/60Hz, 3P/N/PE |
| Size | 12192 × 2438 × 2896 mm |
| Weight | 27600 kg |
| Noise Level | 75.0 dB |
| Condition | New |
| Minimum order | 1 |
| Miner Capacity | 396 standard T-type Antminer hydro miners or 242 2U-type Antminer S23e U2H miners |
| Supported Miners | Standard Antminer S19/S21/S23 Hyd series | New 2U Antminer S23e U2H |
| Container Dimensions | 12192 × 2438 × 2896 mm |
| PUE | 1.031 at 25°C ambient and 35°C supply liquid temperature |
| Supply-to-Ambient Temperature | ≤5°C |
| Container Certification | Classification Society Certification |
| Safety Certifications | NFPA 79:2024 | UL 508A:2018 R7.22 | CSA C22.2 No. 301:23 | UL 2011:2022 | UL 2755:2018 | EN 60204-1:2018 | EN ISO 12100:2010 |
| Product Life | 10 years |
| Rated Power | 2100 kW |
| Maximum Supported Input Power | 2500 kW |
| Maximum Supported Input Current | 960 A × 4 |
Share your miner models and quantities so compatibility can be checked against the proposed configuration.
The catalog lists 2000 kW and 380–480V, 50/60Hz, 3P/N/PE. Have your electrical designer confirm site capacity and connection details for the intended fleet.
The displayed unit price covers the system, not the miners. Confirm included components, freight, installation and lead time in the quote.
Our experts can help you build a more efficient and profitable operation.
| Maximum Current per Miner Slot |
|---|
| 25 A |
| External Interface | DN125 Tri-Clamp ISO 139.7 |
|---|
| Flow Rate | >86 × 2 m³/h |
|---|
| Circulation Pump Power | 30 kW × 2 |
|---|
| Cooling Unit | Dry cooler + water curtain |
|---|
| Heat Dissipation Capacity | 2000 kW |
|---|
| Cooling Fan Power | 4.1 kW × 22 |
|---|
| Water Curtain Pump Power | 1.5 kW × 2 |
|---|
| Coolant Usage | 3.2 m³ |
|---|
| Altitude | ≤2000 m |
|---|
| Manufacturer | BITMAIN |
|---|
| Cooling Type | Hydro Cooling |
|---|
| Warranty | 365 days from shipping date |
|---|
| Lead Time | October 20-31 |
|---|